Controller issues only
This area is for qualified personal onlyNote: Pump ON = Roof sensor °C minus Inlet sensor °C (differential value when the solar pump will turn ON). Pump OFF is similar to Pump ON except is the turn off differential.
Pump on at night
Click on flow diagram to the right for logical troubleshooting.Usually a reverse thermosiphon issue, the one-way valve or back flow prevention fails.
Pump not turning off
Beware a 'Pump Off' value that is too low. Min 2°C for pools, 3°C for solar hot waterNo solar harvesting yet sun is shining
Usually water has stopped flowing in the solar loopPump acting strange
Usually normal for stagnation recovery behaviourSuspect Sensor temperature readings
Usually a broken or insulation stripped cable. Might not be visible externally.Ensure sensor cables are securely fastened and protected from damage